EMB

2387-1-7

Product Family:
EMB
Certification:
CE
Refrigerant Type:
R515B
Safety Class:
A1
Capacity Control:
2-Stepped

Application

Nominal Heating Capacity:
145 kW
Nominal Cooling Capacity:
182 kW
Nominal COP Heating:
2.84
Nominal COP Cooling:
4.19
Condenser Outlet Temp.:
65 °C
Evaporator Inlet Temp.:
-4 °C
Lowest Evaporator Temp. To Reach Highest Condenser Temp.:
0 °C
Highest Evaporator Outlet Temp.:
20 °C

Dimensions

Length:
1970 mm
Width:
860 mm
Height:
1895 mm
Weight:
1600 kg

Technical Features

Compressor Type:
Scroll
Energy Source:
Ground, Waste heat, Water
Special Features:
Internal pumps
GWP:
293

The Energy Machines™ EMB models are designed for space heating, warm tap water production, and comfort cooling. They contain either one or two refrigerant circuits with two compressors in each.

The EMB models operate with either one or two heat source circuits containing brine. These circuits have an integrated circulation pump and switch between the production of hot tap water and the production of heat.

The EMB comes as a completely reversible heat pump in one unit.

Documentation

Check an operating point

Estimated from machine model
Cold side (source)

11 to 18.4 °C

7.5 to 14 °C

Hot side (sink)

23 to 41.5 °C

38.5 to 57 °C

Compressors runningSet load by

2 of 2 compressors · about 100 %

Fluids: ethanol - water 26 % (cold side), water (hot side) · Compressor input only

Up to date

Operating envelope

−20 °C−15 °C−10 °C−5 °C0 °C5 °C10 °C15 °C20 °C25 °C10 °C20 °C30 °C40 °C50 °C60 °C70 °CTe – evaporating temperatureTc – condensing temperatureCOP 4COP 6COP 8COP 10COP 121COP 5.26 · 227 kW

Operating points

PointSource in → outSink in → outLoadTe / TcHeating capacityElectrical inputCOP heatingNotesActions
115.0 → 10.0 °C37.0 → 43.0 °C2 of 2 compressors5.4 / 44.9 °C227 kW43 kW5.26Compressor input only
Estimated from machine model. Engineering review required.

The EMB 2387-1-7 is a scroll-compressor heat pump using R515B (safety class A1). It delivers 145 kW heating at 1 °C → -3 °C ethanol 26% (source) and 47 °C → 53 °C water (sink). Catalogue maximum condenser outlet: 65 °C (not verified by this datasheet).

Does the project accept an A2L refrigerant? The EMB 2387-1-4 is the R1234ze variant. Both share one datasheet performance table, which shows no performance advantage for either. Confirm site and safety requirements with engineering.

Rating conditions

2 rated points · datasheet V3.1

Rated points from datasheet V3.1 (2026-06-04). These are rating conditions, not operating limits.

Rating conditions
Mode / configurationSource fluid in → outSink fluid in → outSpeed / load pointCapacityElectrical input / boundaryCOPDatasheet revision
Heating
Standard
ethanol 26%
1 °C → -3 °C
water
47 °C → 53 °C
Not stated145 kW51.3 kW
Compressors only
2.84V3.1
2026-06-04
Cooling
Standard
ethanol 26%
15 °C → 10 °C
water
37 °C → 43 °C
Not stated182 kW43.4 kW
Compressors only
4.19V3.1
2026-06-04

Source is the evaporator side and sink is the condenser side in both modes. Electrical input is compressor power at the rated operating point, not for sizing the electrical supply. The datasheet does not specify a test standard or a simultaneous heating-and-cooling rating.