EMHP

44-44-2-4

Product Family:
EMHP
Certification:
CE
Refrigerant Type:
R1234ze
Safety Class:
A2L
Capacity Control:
Frequency controlled, PWM

Application

Nominal Heating Capacity:
98 kW
Nominal Cooling Capacity:
141 kW
Nominal COP Heating:
3.25
Nominal COP Cooling:
3.95
Condenser Outlet Temp.:
90 °C
Evaporator Inlet Temp.:
-5 °C
Lowest Evaporator Temp. To Reach Highest Condenser Temp.:
0 °C
Highest Evaporator Outlet Temp.:
35 °C

Dimensions

Length:
1970 mm
Width:
875 mm
Height:
1845 mm
Weight:
1550 kg

Technical Features

Compressor Type:
Reciprocating
Energy Source:
Ground, Waste heat, Water
Special Features:
Frequency option, High capacity control range, Internal pumps
GWP:
1.37

This Energy Machines™ EMHP model contains two refrigerant circuits with a semi-hermetic reciprocating compressor in each. The two refrigerant circuits are completely independent, ensuring the stability of the heating supply.

The EMHP model is specifically designed for heating and cooling purposes. It can handle large pressure drops on the water side using the machine’s internal water pumps.

The EMHP comes as a complete heat pump and cooling system in one unit.

Documentation

Check an operating point

Estimated from machine model
Cold side (source)
Hot side (sink)
Compressors running

2 of 2 compressors · about 100 %

Fluids: ethanol - water 26 % (cold side), water (hot side) · Compressor input only

Up to date

Operating envelope

-20 °C-15 °C-10 °C-5 °C0 °C5 °C10 °C15 °C20 °C25 °C30 °C10 °C20 °C30 °C40 °C50 °C60 °C70 °C80 °C90 °CTe – evaporating temperatureTc – condensing temperatureCOP 2COP 4COP 6COP 81COP 5.00 · 179 kW

Operating points

Columns
Inputs
Results
Saved in this browser.
PointSource in → outSink in → outLoadTe / TcHeating capacityElectrical inputCOP heatingNotesActions
115.0 → 10.0 °C37.0 → 43.0 °C2 of 2 compressors5.7 / 44.9 °C179 kW36 kW5.00Compressor input only
Estimated from machine model. Engineering review required.

The EMHP 44-44-2-4 is a reciprocating-compressor heat pump using R1234ze (safety class A2L). Catalogue nominal heating capacity: 98 kW. Catalogue maximum condenser outlet: 90 °C (not verified by this datasheet).

Need an A1 refrigerant? The EMHP 44-44-2-7 is the R515B variant. Both share one datasheet performance table, which shows no performance advantage for either. Confirm site and safety requirements with engineering.

Rating conditions

Rating conditions
Mode / configurationSource fluid in → outSink fluid in → outSpeed / load pointCapacityElectrical input / boundaryCOPDatasheet revision
Datasheet rating points are awaiting engineering confirmation. Request a confirmed operating point for your project.

Source is the evaporator side and sink is the condenser side in both modes. Electrical input is compressor power at the rated operating point, not for sizing the electrical supply. The datasheet does not specify a test standard or a simultaneous heating-and-cooling rating.