EMHP

60-60-2-4

Product Family:
EMHP
Certification:
CE
Refrigerant Type:
R1234ze
Safety Class:
A2L
Capacity Control:
Frequency controlled, PWM

Application

Nominal Heating Capacity:
135 kW
Nominal Cooling Capacity:
202 kW
Nominal COP Heating:
3.12
Nominal COP Cooling:
3.92
Condenser Outlet Temp.:
90 °C
Evaporator Inlet Temp.:
-5 °C
Lowest Evaporator Temp. To Reach Highest Condenser Temp.:
0 °C
Highest Evaporator Outlet Temp.:
35 °C

Dimensions

Length:
1970 mm
Width:
875 mm
Height:
1845 mm
Weight:
1750 kg

Technical Features

Compressor Type:
Reciprocating
Energy Source:
Ground, Waste heat, Water
Special Features:
Frequency option, High capacity control range, Internal pumps
GWP:
1.37

This Energy Machines™ EMHP model contains two refrigerant circuits with a semi-hermetic reciprocating compressor in each. The two refrigerant circuits are completely independent, ensuring the stability of the heating supply.

The EMHP model is specifically designed for heating and cooling purposes. It can handle large pressure drops on the water side using the machine’s internal water pumps.

The EMHP comes as a complete heat pump and cooling system in one unit.

EMHW

  • EMHW products are designed for production of warm tap water with serial connected heat exchangers.
  • Refrigerant: EMHW does not contain refrigerant circuits.
  • Nominal heating capacity: 130-500 kW

EMCW

  • EMCW products are similar to EMHW products, but designed for cooling water or liquids.
  • Refrigerant: EMCW does not contain refrigerant circuits.
  • Nominal cooling capacity: Defined by request

EM Control

  • Seamless control and automation

EM Cloud

  • Flexible optimization from anywhere

EM VerifyOptional add-on

  • Transparent heat pump performance

Documentation

Check an operating point

Estimated from machine model
Cold side (source)

11 to 18.9 °C

6.9 to 14 °C

Hot side (sink)

23 to 41.5 °C

38.5 to 57 °C

Compressors runningSet load by

2 of 2 compressors · about 100 %

Fluids: ethanol - water 26 % (cold side), water (hot side) · Compressor input only

Up to date

Operating envelope

−20 °C−15 °C−10 °C−5 °C0 °C5 °C10 °C15 °C20 °C25 °C30 °C10 °C20 °C30 °C40 °C50 °C60 °C70 °C80 °C90 °CTe – evaporating temperatureTc – condensing temperatureCOP 2COP 4COP 6COP 81COP 4.97 · 255 kW

Operating points

PointSource in → outSink in → outLoadTe / TcHeating capacityElectrical inputCOP heatingNotesActions
115.0 → 10.0 °C37.0 → 43.0 °C2 of 2 compressors6.6 / 45.5 °C255 kW51 kW4.97Compressor input only
Estimated from machine model. Engineering review required.

Seasonal heating efficiency (SCOP)

This machine over a heating season, by the EN 14825 bin method.

Seasonal cooling efficiency (SEER)

This machine over a cooling season, by the EN 14825 bin method.

Standard rating conditions

This machine at full load at the rating conditions of EN 14511, ISO 13256-2, AHRI 550/590 and ASHRAE.