EMHP

80-80-2-7

Product Family:
EMHP
Certification:
CE
Refrigerant Type:
R515B
Safety Class:
A1
Capacity Control:
Frequency controlled, PWM

Application

Nominal Heating Capacity:
181 kW
Nominal Cooling Capacity:
270 kW
Nominal COP Heating:
3.11
Nominal COP Cooling:
3.92
Condenser Outlet Temp.:
90 °C
Evaporator Inlet Temp.:
-5 °C
Lowest Evaporator Temp. To Reach Highest Condenser Temp.:
0 °C
Highest Evaporator Outlet Temp.:
35 °C

Dimensions

Length:
2950 mm
Width:
1160 mm
Height:
1845 mm
Weight:
2950 kg

Technical Features

Compressor Type:
Reciprocating
Energy Source:
Ground, Waste heat, Water
Special Features:
Frequency option, High capacity control range, Internal pumps
GWP:
293

This Energy Machines™ EMHP model contains two refrigerant circuits with a semi-hermetic reciprocating compressor in each. The two refrigerant circuits are completely independent, ensuring the stability of the heating supply.

The EMHP model is specifically designed for heating and cooling purposes. It can handle large pressure drops on the water side using the machine’s internal water pumps.

The EMHP comes as a complete heat pump and cooling system in one unit.

Documentation

Check an operating point

Estimated from related machine
Cold side (source)
Hot side (sink)
Compressors running

2 of 2 compressors · about 100 %

Fluids: ethanol - water 26 % (cold side), water (hot side) · Compressor input only

Up to date

Operating envelope

-25 °C-20 °C-15 °C-10 °C-5 °C0 °C5 °C10 °C15 °C20 °C25 °C30 °C35 °C40 °C10 °C20 °C30 °C40 °C50 °C60 °C70 °C80 °C90 °C100 °CTe – evaporating temperatureTc – condensing temperatureCOP 2COP 4COP 61COP 2.40 · 196 kW

Operating points

Columns
Inputs
Results
Saved in this browser.
PointSource in → outSink in → outLoadTe / TcHeating capacityElectrical inputCOP heatingNotesActions
111.0 → 6.0 °C60.0 → 80.0 °C2 of 2 compressors2.9 / 79.0 °C196 kW82 kW2.40Outside calibrated temperature differencesCompressor input only
Estimated from related machine. Engineering review required.

The EMHP 80-80-2-7 is a reciprocating-compressor heat pump using R515B (safety class A1). Catalogue nominal heating capacity: 181 kW. Catalogue maximum condenser outlet: 90 °C (not verified by this datasheet).

Does the project accept an A2L refrigerant? The EMHP 80-80-2-4 is the R1234ze variant. Both share one datasheet performance table, which shows no performance advantage for either. Confirm site and safety requirements with engineering.

Rating conditions

Rating conditions
Mode / configurationSource fluid in → outSink fluid in → outSpeed / load pointCapacityElectrical input / boundaryCOPDatasheet revision
Datasheet rating points are awaiting engineering confirmation. Request a confirmed operating point for your project.

Source is the evaporator side and sink is the condenser side in both modes. Electrical input is compressor power at the rated operating point, not for sizing the electrical supply. The datasheet does not specify a test standard or a simultaneous heating-and-cooling rating.