EMT

2490-1-7-FT

Product Family:
EMT
Certification:
CE
Refrigerant Type:
R515B
Safety Class:
A1
Capacity Control:
Frequency controlled

Application

Nominal Heating Capacity:
1178 kW
Nominal Cooling Capacity:
1024 kW
Nominal COP Heating:
4.47
Nominal COP Cooling:
3.91
Condenser Outlet Temp.:
55 °C
Evaporator Inlet Temp.:
0 °C
Lowest Evaporator Temp. To Reach Highest Condenser Temp.:
7 °C
Highest Evaporator Outlet Temp.:
30 °C

Dimensions

Length:
3040 mm
Width:
1810 mm
Height:
2410 mm
Weight:
4600 kg

Technical Features

Compressor Type:
Turbo
Energy Source:
Waste heat, Water
Special Features:
Economizer, Oil-free
GWP:
293

This Energy Machines™ EMT model contains two oil-free centrifugal compressors in one refrigerant circuit. The compressor is classified as a non-positive displacement compressor.

This model is equipped with a flash tank, increasing its energy efficiency. The machine’s evaporator and condenser are shell-and-tube heat exchangers. The evaporator operates with a flooded evaporation technique.

These components work together to create a powerful and efficient machine.

Documentation

Check an operating point

Indicative — engineering review required
Cold side (source)
Hot side (sink)
Heating capacity

1178 kW · 100 % of full load at this operating point

Up to date

Operating envelope

-10 °C-5 °C0 °C5 °C10 °C15 °C20 °C25 °C30 °C20 °C30 °C40 °C50 °C60 °CTe – evaporating temperatureTc – condensing temperatureCOP 4COP 6COP 8COP 101COP 4.47 · 1178 kW

Operating points

Columns
Inputs
Results
Saved in this browser.
PointSource in → outSink in → outLoadTe / TcHeating capacityElectrical inputCOP heatingNotesActions
110.0 → 7.0 °C40.0 → 45.0 °CFull load4.0 / 48.0 °C1178 kW264 kW4.47–
Indicative values. Engineering review required.

The EMT 2490-1-7-FT is a turbo-compressor heat pump using R515B (safety class A1). Catalogue nominal heating capacity: 1178 kW. Catalogue maximum condenser outlet: 55 °C (not verified by this datasheet).

Does the project accept an A2L refrigerant? The EMT 2490-1-4-FT is the R1234ze variant. Both share one datasheet performance table, which shows no performance advantage for either. Confirm site and safety requirements with engineering.

Rating conditions

Rating conditions
Mode / configurationSource fluid in → outSink fluid in → outSpeed / load pointCapacityElectrical input / boundaryCOPDatasheet revision
Datasheet rating points are awaiting engineering confirmation. Request a confirmed operating point for your project.

Source is the evaporator side and sink is the condenser side in both modes. Electrical input is compressor power at the rated operating point, not for sizing the electrical supply. The datasheet does not specify a test standard or a simultaneous heating-and-cooling rating.