EMT

4285-1-4-FT

Product Family:
EMT
Certification:
CE
Refrigerant Type:
R1234ze
Safety Class:
A2L
Capacity Control:
Frequency controlled

Application

Nominal Heating Capacity:
1388 kW
Nominal Cooling Capacity:
1102 kW
Nominal COP Heating:
3.68
Nominal COP Cooling:
3.44
Condenser Outlet Temp.:
65 °C
Evaporator Inlet Temp.:
-12 °C
Lowest Evaporator Temp. To Reach Highest Condenser Temp.:
7 °C
Highest Evaporator Outlet Temp.:
27 °C

Dimensions

Length:
4350 mm
Width:
1830 mm
Height:
2406 mm
Weight:
9000 kg

Technical Features

Compressor Type:
Turbo
Energy Source:
Ground, Waste heat, Water
Special Features:
Economizer, Oil-free
GWP:
1.37

This Energy Machines™ model contains four oil-free centrifugal compressors in one refrigerant circuit. The compressors are classified as nonpositive displacement compressors.

This model is equipped with a flash tank, increasing its energy efficiency. The machine’s evaporator and condenser are shell-and-tube heat exchangers. The evaporator operates with a flooded evaporation technique.

These components work together to create a powerful and efficient machine.

Documentation

Check an operating point

Indicative — engineering review required
Cold side (source)
Hot side (sink)
Heating capacity

1388 kW · 100 % of full load at this operating point

Up to date

Operating envelope

-25 °C-20 °C-15 °C-10 °C-5 °C0 °C5 °C10 °C15 °C20 °C25 °C30 °C20 °C30 °C40 °C50 °C60 °C70 °CTe – evaporating temperatureTc – condensing temperatureCOP 4COP 5COP 6COP 71COP 3.68 · 1388 kW

Operating points

Columns
Inputs
Results
Saved in this browser.
PointSource in → outSink in → outLoadTe / TcHeating capacityElectrical inputCOP heatingNotesActions
112.0 → 7.0 °C57.0 → 63.0 °CFull load4.0 / 66.0 °C1388 kW377 kW3.68About ±5 % capacity, ±10 % COP
Indicative values. Engineering review required.

The EMT 4285-1-4-FT is a turbo-compressor heat pump using R1234ze (safety class A2L). Catalogue nominal heating capacity: 1388 kW. Catalogue maximum condenser outlet: 65 °C (not verified by this datasheet).

Need an A1 refrigerant? The EMT 4285-1-7-FT is the R515B variant. Both share one datasheet performance table, which shows no performance advantage for either. Confirm site and safety requirements with engineering.

Rating conditions

Rating conditions
Mode / configurationSource fluid in → outSink fluid in → outSpeed / load pointCapacityElectrical input / boundaryCOPDatasheet revision
Datasheet rating points are awaiting engineering confirmation. Request a confirmed operating point for your project.

Source is the evaporator side and sink is the condenser side in both modes. Electrical input is compressor power at the rated operating point, not for sizing the electrical supply. The datasheet does not specify a test standard or a simultaneous heating-and-cooling rating.