EMT

4380-1-4-FT

Product Family:
EMT
Certification:
CE
Refrigerant Type:
R1234ze
Safety Class:
A2L
Capacity Control:
Frequency controlled

Application

Nominal Heating Capacity:
1902 kW
Nominal Cooling Capacity:
1552 kW
Nominal COP Heating:
3.73
Nominal COP Cooling:
3.77
Condenser Outlet Temp.:
65 °C
Evaporator Inlet Temp.:
0 °C
Lowest Evaporator Temp. To Reach Highest Condenser Temp.:
7 °C
Highest Evaporator Outlet Temp.:
30 °C

Dimensions

Length:
N/A
Width:
N/A
Height:
N/A
Weight:
N/A

Technical Features

Compressor Type:
Turbo
Energy Source:
Waste heat, Water
Special Features:
Economizer, Oil-free
GWP:
1.37

This Energy Machines™ model contains four oil-free centrifugal compressors in one refrigerant circuit. The compressors are classified as nonpositive displacement compressors.

This model is equipped with a flash tank, increasing its energy efficiency. The machine’s evaporator and condenser are shell-and-tube heat exchangers. The evaporator operates with a flooded evaporation technique.

These components work together to create a powerful and efficient machine.

Documentation

Check an operating point

Indicative — engineering review required
Cold side (source)
Hot side (sink)
Heating capacity

1902 kW · 100 % of full load at this operating point

Up to date

Operating envelope

-15 °C-10 °C-5 °C0 °C5 °C10 °C15 °C20 °C25 °C30 °C20 °C30 °C40 °C50 °C60 °C70 °CTe – evaporating temperatureTc – condensing temperatureCOP 4COP 5COP 6COP 7COP 81COP 3.73 · 1902 kW

Operating points

Columns
Inputs
Results
Saved in this browser.
PointSource in → outSink in → outLoadTe / TcHeating capacityElectrical inputCOP heatingNotesActions
112.0 → 7.0 °C57.0 → 63.0 °CFull load4.0 / 66.0 °C1902 kW510 kW3.73About ±5 % capacity, ±10 % COP
Indicative values. Engineering review required.

The EMT 4380-1-4-FT is a turbo-compressor heat pump using R1234ze (safety class A2L). Catalogue nominal heating capacity: 1902 kW. Catalogue maximum condenser outlet: 65 °C (not verified by this datasheet).

Need an A1 refrigerant? The EMT 4380-1-7-FT is the R515B variant. Both share one datasheet performance table, which shows no performance advantage for either. Confirm site and safety requirements with engineering.

Rating conditions

Rating conditions
Mode / configurationSource fluid in → outSink fluid in → outSpeed / load pointCapacityElectrical input / boundaryCOPDatasheet revision
Datasheet rating points are awaiting engineering confirmation. Request a confirmed operating point for your project.

Source is the evaporator side and sink is the condenser side in both modes. Electrical input is compressor power at the rated operating point, not for sizing the electrical supply. The datasheet does not specify a test standard or a simultaneous heating-and-cooling rating.