Engineering guidance
How to interpret heat-pump COP and temperature lift
Heating COP is useful heat output divided by electrical input, both at the same operating case and boundary. A COP is only comparable when the source and sink temperatures, the load and the electrical scope are stated with it.
Equipment COP and system COP
Illustrative figures, not an Energy Machines rating: a heat pump delivers 400 kW of heat with 100 kW of electrical input at one fixed operating case. Equipment COP = 400 / 100 = 4.0. If the source and distribution pumps draw another 20 kW, system COP = 400 / (100 + 20) ≈ 3.3.
In a real calculation, take every power at the same temperatures and load. The rated power input given for electrical connection sizing is not the input at a duty point; do not use it as the COP denominator.
The EMB points in the table below state heating capacity, compressor electrical input and COP at the same operating case. Their boundary is the compressors only; add pumps and auxiliaries before you compare them with a system COP.
Temperature lift and part load
Temperature lift is the difference between the refrigerant condensing and evaporating temperatures. It is larger than the difference between the fluid temperatures, because each heat exchanger adds an approach. More lift means more compressor work per kW of heat, so COP falls as supply temperature rises or source temperature drops.
The ideal (Carnot) COP uses absolute refrigerant temperatures and gives a theoretical upper bound. It does not replace declared or measured performance.
Part load is operation below design output. Ask for the minimum stable capacity and how several units are sequenced.
Comparing datasheets and seasonal figures
Compare COPs only at the same fluid temperatures, flows, fluid composition, load or speed, and configuration. Check whether the electrical input covers the compressors only or also drives, controls and pumps.
SCOP and SPF are seasonal figures. Each needs a stated calculation method, climate or load profile and auxiliary-energy boundary, and a SCOP from one method does not describe every industrial installation. An annual figure comes from time-weighted energy, not from averaging a few COP points.
Models and documented rating conditions
Rating points as printed in each datasheet. Each row describes one operating point, not the full operating envelope. Missing electrical boundaries, loads or speeds are marked in the table.
| Model / refrigerant | Source inlet → outlet | Heated water inlet → outlet | Declared operating point | Thermal capacity / COP | Document / boundary |
|---|---|---|---|---|---|
| EMB 2295-1-4 R1234ze | ethanol 26% 1 → -3 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 114 kW COP: Pending confirmation | Datasheet V3.1 · 2026-06-04 · EN · p. 2 Electrical input: 41.5 kW (compressors only) COP scope: compressors only Test standard: Not stated |
| EMB 2295-1-7 R515B | ethanol 26% 1 → -3 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 114 kW COP: Pending confirmation | Datasheet V3.1 · 2026-06-04 · EN · p. 2 Electrical input: 41.5 kW (compressors only) COP scope: compressors only Test standard: Not stated |
| EMB 2387-1-4 R1234ze | ethanol 26% 1 → -3 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 145 kW COP: 2.84 | Datasheet V3.1 · 2026-06-04 · EN · p. 2 Electrical input: 51.3 kW (compressors only) COP scope: compressors only Test standard: Not stated |
| EMB 2387-1-7 R515B | ethanol 26% 1 → -3 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 145 kW COP: 2.84 | Datasheet V3.1 · 2026-06-04 · EN · p. 2 Electrical input: 51.3 kW (compressors only) COP scope: compressors only Test standard: Not stated |
| EMB 2480-1-4 R1234ze | ethanol 26% 1 → -3 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 175 kW COP: 2.87 | Datasheet V3.1 · 2026-06-04 · EN · p. 2 Electrical input: 61 kW (compressors only) COP scope: compressors only Test standard: Not stated |
| EMB 2480-1-7 R515B | ethanol 26% 1 → -3 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 175 kW COP: 2.87 | Datasheet V3.1 · 2026-06-04 · EN · p. 2 Electrical input: 61 kW (compressors only) COP scope: compressors only Test standard: Not stated |
| EMB 4295-2-4 R1234ze | ethanol 26% 1 → -3 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 229 kW COP: Pending confirmation | Datasheet V3.1 · 2026-06-04 · EN · p. 2 Electrical input: 83 kW (compressors only) COP scope: compressors only Test standard: Not stated |
| EMB 4295-2-7 R515B | ethanol 26% 1 → -3 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 229 kW COP: Pending confirmation | Datasheet V3.1 · 2026-06-04 · EN · p. 2 Electrical input: 83 kW (compressors only) COP scope: compressors only Test standard: Not stated |
| EMB 4387-2-4 R1234ze | ethanol 26% 1 → -3 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 289 kW COP: Pending confirmation | Datasheet V3.1 · 2026-06-04 · EN · p. 2 Electrical input: 102.5 kW (compressors only) COP scope: compressors only Test standard: Not stated |
| EMB 4387-2-7 R515B | ethanol 26% 1 → -3 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 289 kW COP: Pending confirmation | Datasheet V3.1 · 2026-06-04 · EN · p. 2 Electrical input: 102.5 kW (compressors only) COP scope: compressors only Test standard: Not stated |
| EMB 4480-2-4 R1234ze | ethanol 26% 1 → -3 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 350 kW COP: 2.87 | Datasheet V3.1 · 2026-06-04 · EN · p. 2 Electrical input: 122.1 kW (compressors only) COP scope: compressors only Test standard: Not stated |
| EMB 4480-2-7 R515B | ethanol 26% 1 → -3 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 350 kW COP: 2.87 | Datasheet V3.1 · 2026-06-04 · EN · p. 2 Electrical input: 122.1 kW (compressors only) COP scope: compressors only Test standard: Not stated |