Engineering guidance
How oil-free turbo heat pumps work and where they fit
An oil-free centrifugal compressor raises refrigerant pressure with a rotating impeller; in EMT heat pumps the shaft runs in magnetic bearings, with no compressor oil circuit. Select on temperature lift and load profile, and note that oil-free does not mean maintenance-free.
How centrifugal compression differs
Scroll and reciprocating compressors trap a volume of gas and reduce it. A centrifugal compressor accelerates the gas in the impeller and converts that velocity into pressure in the diffuser. There is no general efficiency ranking between the types. Compare complete machines at your duty: capacity, turndown, operating map and service capability.
Part load and temperature lift
EMT compressors run on a variable-speed drive that follows demand. Check four limits together: minimum stable load, permitted pressure ratio, the source temperature range and the sequencing of several units. A single nominal COP says little about a year of operation; ask for performance at the part-load operating cases you expect.
Depending on the model, the EMT heating points in the table below use water at 12 → 7 °C on the cold side and 47 → 53 °C or 57 → 63 °C on the hot side. COP values not yet confirmed are marked ‘Withheld pending confirmation’.
Check the model documentation
Compressor count and refrigerant-circuit count vary across the range and are different things. ECO and FT name documented model variants; the letters do not tell you the circuit layout, the redundancy or whether performance is interchangeable. Check the exact model against its datasheet and hydraulic drawing.
EMT machines use shell-and-tube heat exchangers with flooded evaporation. ‘Flooded’ describes the refrigerant side; it does not mean any process fluid can be connected. Check water quality, freeze protection, cleaning access and pressure drop for the selected arrangement.
Models and documented rating conditions
Rating points as printed in each datasheet. Each row describes one operating point, not the full operating envelope. Missing electrical boundaries, loads or speeds are marked in the table.
| Model / refrigerant | Source inlet → outlet | Heated water inlet → outlet | Declared operating point | Thermal capacity / COP | Document / boundary |
|---|---|---|---|---|---|
| EMT 1230-1-4-ECO R1234ze | water 12 → 7 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 265 kW COP: Pending confirmation | Datasheet V1.8 · 2025-12-04 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMT 1230-1-7-ECO R515B | water 12 → 7 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 265 kW COP: Pending confirmation | Datasheet V1.8 · 2025-12-04 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMT 1285-1-4-ECO R1234ze | water 12 → 7 °C | water 57 → 63 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 347 kW COP: Pending confirmation | Datasheet V1.8 · 2025-12-04 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMT 1285-1-7-ECO R515B | water 12 → 7 °C | water 57 → 63 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 347 kW COP: Pending confirmation | Datasheet V1.8 · 2025-12-04 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMT 1310-1-4-ECO R1234ze | water 12 → 7 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 379 kW COP: Pending confirmation | Datasheet V1.8 · 2025-12-04 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMT 1310-1-7-ECO R515B | water 12 → 7 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 379 kW COP: Pending confirmation | Datasheet V1.8 · 2025-12-04 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMT 1380-1-4-ECO R1234ze | water 12 → 7 °C | water 57 → 63 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 476 kW COP: Pending confirmation | Datasheet V1.8 · 2025-12-04 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMT 1380-1-7-ECO R515B | water 12 → 7 °C | water 57 → 63 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 476 kW COP: Pending confirmation | Datasheet V1.8 · 2025-12-04 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMT 1490-1-4-ECO R1234ze | water 12 → 7 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 589 kW COP: Pending confirmation | Datasheet V1.8 · 2025-12-04 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMT 1490-1-7-ECO R515B | water 12 → 7 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 589 kW COP: Pending confirmation | Datasheet V1.8 · 2025-12-04 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMT 2230-1-4-FT R1234ze | water 12 → 7 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 530 kW COP: Pending confirmation | Datasheet V1.8 · 2025-12-04 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMT 2230-1-7-FT R515B | water 12 → 7 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 530 kW COP: Pending confirmation | Datasheet V1.8 · 2025-12-04 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMT 2230-2-4-ECO R1234ze | water 12 → 7 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 530 kW COP: Pending confirmation | Datasheet V1.8 · 2025-12-04 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMT 2230-2-7-ECO R515B | water 12 → 7 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 530 kW COP: Pending confirmation | Datasheet V1.8 · 2025-12-04 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMT 2285-1-4-FT R1234ze | water 12 → 7 °C | water 57 → 63 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 694 kW COP: Pending confirmation | Datasheet V1.7 · 2024-12-23 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMT 2285-1-7-FT R515B | water 12 → 7 °C | water 57 → 63 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 694 kW COP: Pending confirmation | Datasheet V1.7 · 2024-12-23 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMT 2285-2-4-ECO R1234ze | water 12 → 7 °C | water 57 → 63 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 694 kW COP: Pending confirmation | Datasheet V1.7 · 2024-12-23 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMT 2285-2-7-ECO R515B | water 12 → 7 °C | water 57 → 63 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 694 kW COP: Pending confirmation | Datasheet V1.7 · 2024-12-23 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMT 2310-1-4-FT R1234ze | water 12 → 7 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 758 kW COP: Pending confirmation | Datasheet V1.7 · 2024-12-23 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMT 2310-1-7-FT R515B | water 12 → 7 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 758 kW COP: Pending confirmation | Datasheet V1.7 · 2024-12-23 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMT 2310-2-4-ECO R1234ze | water 12 → 7 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 758 kW COP: Pending confirmation | Datasheet V1.7 · 2024-12-23 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMT 2310-2-7-ECO R515B | water 12 → 7 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 758 kW COP: Pending confirmation | Datasheet V1.7 · 2024-12-23 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMT 2380-1-4-FT R1234ze | water 12 → 7 °C | water 57 → 63 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 951 kW COP: Pending confirmation | Datasheet V1.7 · 2024-12-23 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMT 2380-1-7-FT R515B | water 12 → 7 °C | water 57 → 63 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 951 kW COP: Pending confirmation | Datasheet V1.7 · 2024-12-23 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMT 2380-2-4-ECO R1234ze | water 12 → 7 °C | water 57 → 63 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 951 kW COP: Pending confirmation | Datasheet V1.7 · 2024-12-23 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMT 2380-2-7-ECO R515B | water 12 → 7 °C | water 57 → 63 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 951 kW COP: Pending confirmation | Datasheet V1.7 · 2024-12-23 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMT 2490-1-4-FT R1234ze | water 12 → 7 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 1,178 kW COP: Pending confirmation | Datasheet V1.7 · 2024-12-23 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMT 2490-1-7-FT R515B | water 12 → 7 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 1,178 kW COP: Pending confirmation | Datasheet V1.7 · 2024-12-23 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMT 2490-2-4-ECO R1234ze | water 12 → 7 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 1,178 kW COP: Pending confirmation | Datasheet V1.7 · 2024-12-23 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMT 2490-2-7-ECO R515B | water 12 → 7 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 1,178 kW COP: Pending confirmation | Datasheet V1.7 · 2024-12-23 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMT 3285-1-4-FT R1234ze | water 12 → 7 °C | water 57 → 63 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 1,041 kW COP: Pending confirmation | Datasheet V1.8 · 2025-12-04 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMT 3285-1-7-FT R515B | water 12 → 7 °C | water 57 → 63 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 1,041 kW COP: Pending confirmation | Datasheet V1.8 · 2025-12-04 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMT 4230-1-4-FT R1234ze | water 12 → 7 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 1,060 kW COP: Pending confirmation | Datasheet V1.7 · 2024-12-23 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMT 4230-1-7-FT R515B | water 12 → 7 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 1,060 kW COP: Pending confirmation | Datasheet V1.7 · 2024-12-23 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMT 4285-1-4-FT R1234ze | water 12 → 7 °C | water 57 → 63 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 1,388 kW COP: Pending confirmation | Datasheet V1.7 · 2024-12-23 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMT 4285-1-7-FT R515B | water 12 → 7 °C | water 57 → 63 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 1,388 kW COP: Pending confirmation | Datasheet V1.7 · 2024-12-23 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMT 4310-1-4-FT R1234ze | water 12 → 7 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 1,516 kW COP: Pending confirmation | Datasheet V1.7 · 2024-12-23 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMT 4310-1-7-FT R515B | water 12 → 7 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 1,516 kW COP: Pending confirmation | Datasheet V1.7 · 2024-12-23 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMT 4380-1-4-FT R1234ze | water 12 → 7 °C | water 57 → 63 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 1,902 kW COP: Pending confirmation | Datasheet V1.7 · 2024-12-23 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMT 4380-1-7-FT R515B | water 12 → 7 °C | water 57 → 63 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 1,902 kW COP: Pending confirmation | Datasheet V1.7 · 2024-12-23 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMT 4490-1-4-FT R1234ze | water 12 → 7 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 2,356 kW COP: Pending confirmation | Datasheet V1.7 · 2024-12-23 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMT 4490-1-7-FT R515B | water 12 → 7 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 2,356 kW COP: Pending confirmation | Datasheet V1.7 · 2024-12-23 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |