Map the waste-heat stream

Log the waste-heat stream through shifts, shutdowns and cleaning cycles, and set it against the heat demand hour by hour. Where both the cooling and the heating are useful, size on the coincident loads, not on the sum of two nominal ratings.

Check the waste-heat fluid for contamination, corrosion and fouling before choosing the separating heat exchanger. Its approach temperature and pressure drop belong in the cold-side conditions you send for the selection.

Temperatures and production continuity

The EMHP and EMB heating points in the table below are rated at 47 → 53 °C on the hot side, with 26% ethanol at 1 → −3 °C on the cold side. EMHP is the family for higher supply temperatures; confirm any duty above the rated point in a project selection.

Define the process temperature tolerance, the backup capacity and how the process keeps running when the heat pump is out of service.

Reference: Sandvik Coromant, Katowice

At the Sandvik Coromant factory in Katowice, Poland, an EMB-based system with borehole thermal energy storage (BTES) uses waste heat from production. It replaced standalone chillers and gas heating. The factory reports 90% lower gas use and 35% lower electricity use. These are site-level results; they give no machine COP and do not show high-temperature process water.

Models and documented rating conditions

Rating points as printed in each datasheet. Each row describes one operating point, not the full operating envelope. Missing electrical boundaries, loads or speeds are marked in the table.

Temperatures are fluid inlet → outlet in °C, capacity in kW. Compare rows only at the same temperatures and boundary.
Model / refrigerantSource inlet → outletHeated water inlet → outletDeclared operating pointThermal capacity / COPDocument / boundary
EMB 2295-1-4
R1234ze
ethanol 26%
1 → -3 °C
water
47 → 53 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
114 kW
COP: Pending confirmation
Datasheet V3.1 · 2026-06-04 · EN · p. 2
Electrical input: 41.5 kW (compressors only)
COP scope: compressors only
Test standard: Not stated
EMB 2295-1-7
R515B
ethanol 26%
1 → -3 °C
water
47 → 53 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
114 kW
COP: Pending confirmation
Datasheet V3.1 · 2026-06-04 · EN · p. 2
Electrical input: 41.5 kW (compressors only)
COP scope: compressors only
Test standard: Not stated
EMB 2387-1-4
R1234ze
ethanol 26%
1 → -3 °C
water
47 → 53 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
145 kW
COP: 2.84
Datasheet V3.1 · 2026-06-04 · EN · p. 2
Electrical input: 51.3 kW (compressors only)
COP scope: compressors only
Test standard: Not stated
EMB 2387-1-7
R515B
ethanol 26%
1 → -3 °C
water
47 → 53 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
145 kW
COP: 2.84
Datasheet V3.1 · 2026-06-04 · EN · p. 2
Electrical input: 51.3 kW (compressors only)
COP scope: compressors only
Test standard: Not stated
EMB 2480-1-4
R1234ze
ethanol 26%
1 → -3 °C
water
47 → 53 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
175 kW
COP: 2.87
Datasheet V3.1 · 2026-06-04 · EN · p. 2
Electrical input: 61 kW (compressors only)
COP scope: compressors only
Test standard: Not stated
EMB 2480-1-7
R515B
ethanol 26%
1 → -3 °C
water
47 → 53 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
175 kW
COP: 2.87
Datasheet V3.1 · 2026-06-04 · EN · p. 2
Electrical input: 61 kW (compressors only)
COP scope: compressors only
Test standard: Not stated
EMB 4295-2-4
R1234ze
ethanol 26%
1 → -3 °C
water
47 → 53 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
229 kW
COP: Pending confirmation
Datasheet V3.1 · 2026-06-04 · EN · p. 2
Electrical input: 83 kW (compressors only)
COP scope: compressors only
Test standard: Not stated
EMB 4295-2-7
R515B
ethanol 26%
1 → -3 °C
water
47 → 53 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
229 kW
COP: Pending confirmation
Datasheet V3.1 · 2026-06-04 · EN · p. 2
Electrical input: 83 kW (compressors only)
COP scope: compressors only
Test standard: Not stated
EMB 4387-2-4
R1234ze
ethanol 26%
1 → -3 °C
water
47 → 53 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
289 kW
COP: Pending confirmation
Datasheet V3.1 · 2026-06-04 · EN · p. 2
Electrical input: 102.5 kW (compressors only)
COP scope: compressors only
Test standard: Not stated
EMB 4387-2-7
R515B
ethanol 26%
1 → -3 °C
water
47 → 53 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
289 kW
COP: Pending confirmation
Datasheet V3.1 · 2026-06-04 · EN · p. 2
Electrical input: 102.5 kW (compressors only)
COP scope: compressors only
Test standard: Not stated
EMB 4480-2-4
R1234ze
ethanol 26%
1 → -3 °C
water
47 → 53 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
350 kW
COP: 2.87
Datasheet V3.1 · 2026-06-04 · EN · p. 2
Electrical input: 122.1 kW (compressors only)
COP scope: compressors only
Test standard: Not stated
EMB 4480-2-7
R515B
ethanol 26%
1 → -3 °C
water
47 → 53 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
350 kW
COP: 2.87
Datasheet V3.1 · 2026-06-04 · EN · p. 2
Electrical input: 122.1 kW (compressors only)
COP scope: compressors only
Test standard: Not stated
EMHP 36-36-2-4
R1234ze
ethanol 26%
1 → -3 °C
water
47 → 53 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
85 kW
COP: Pending confirmation
Datasheet V7.0 · 2026-03-05 · EN · p. 2
Electrical input: Not stated (Not stated)
COP scope: Not stated
Test standard: Not stated
EMHP 36-36-2-7
R515B
ethanol 26%
1 → -3 °C
water
47 → 53 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
85 kW
COP: Pending confirmation
Datasheet V7.0 · 2026-03-05 · EN · p. 2
Electrical input: Not stated (Not stated)
COP scope: Not stated
Test standard: Not stated
EMHP 36F-36F-2-4
R1234ze
ethanol 26%
1 → -3 °C
water
47 → 53 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
100 kW
COP: Pending confirmation
Datasheet V7.0 · 2026-03-05 · EN · p. 2
Electrical input: Not stated (Not stated)
COP scope: Not stated
Test standard: Not stated
EMHP 36F-36F-2-7
R515B
ethanol 26%
1 → -3 °C
water
47 → 53 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
100 kW
COP: Pending confirmation
Datasheet V7.0 · 2026-03-05 · EN · p. 2
Electrical input: Not stated (Not stated)
COP scope: Not stated
Test standard: Not stated
EMHP 44-44-2-4
R1234ze
ethanol 26%
1 → -3 °C
water
47 → 53 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
98 kW
COP: Pending confirmation
Datasheet V7.0 · 2026-03-05 · EN · p. 2
Electrical input: Not stated (Not stated)
COP scope: Not stated
Test standard: Not stated
EMHP 44-44-2-7
R515B
ethanol 26%
1 → -3 °C
water
47 → 53 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
98 kW
COP: Pending confirmation
Datasheet V7.0 · 2026-03-05 · EN · p. 2
Electrical input: Not stated (Not stated)
COP scope: Not stated
Test standard: Not stated
EMHP 44F-44F-2-4
R1234ze
ethanol 26%
1 → -3 °C
water
47 → 53 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
116 kW
COP: Pending confirmation
Datasheet V7.0 · 2026-03-05 · EN · p. 2
Electrical input: Not stated (Not stated)
COP scope: Not stated
Test standard: Not stated
EMHP 44F-44F-2-7
R515B
ethanol 26%
1 → -3 °C
water
47 → 53 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
116 kW
COP: Pending confirmation
Datasheet V7.0 · 2026-03-05 · EN · p. 2
Electrical input: Not stated (Not stated)
COP scope: Not stated
Test standard: Not stated
EMHP 60-60-2-4
R1234ze
ethanol 26%
1 → -3 °C
water
47 → 53 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
135 kW
COP: Pending confirmation
Datasheet V7.0 · 2026-03-05 · EN · p. 2
Electrical input: Not stated (Not stated)
COP scope: Not stated
Test standard: Not stated
EMHP 60-60-2-7
R515B
ethanol 26%
1 → -3 °C
water
47 → 53 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
135 kW
COP: Pending confirmation
Datasheet V7.0 · 2026-03-05 · EN · p. 2
Electrical input: Not stated (Not stated)
COP scope: Not stated
Test standard: Not stated
EMHP 60F-60F-2-4
R1234ze
ethanol 26%
1 → -3 °C
water
47 → 53 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
161 kW
COP: Pending confirmation
Datasheet V7.0 · 2026-03-05 · EN · p. 2
Electrical input: Not stated (Not stated)
COP scope: Not stated
Test standard: Not stated
EMHP 60F-60F-2-7
R515B
ethanol 26%
1 → -3 °C
water
47 → 53 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
161 kW
COP: Pending confirmation
Datasheet V7.0 · 2026-03-05 · EN · p. 2
Electrical input: Not stated (Not stated)
COP scope: Not stated
Test standard: Not stated
EMHP 80-80-2-4
R1234ze
ethanol 26%
1 → -3 °C
water
47 → 53 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
181 kW
COP: Pending confirmation
Datasheet V7.0 · 2026-03-05 · EN · p. 2
Electrical input: Not stated (Not stated)
COP scope: Not stated
Test standard: Not stated
EMHP 80-80-2-7
R515B
ethanol 26%
1 → -3 °C
water
47 → 53 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
181 kW
COP: Pending confirmation
Datasheet V7.0 · 2026-03-05 · EN · p. 2
Electrical input: Not stated (Not stated)
COP scope: Not stated
Test standard: Not stated
EMHP 80F-80F-2-4
R1234ze
ethanol 26%
1 → -3 °C
water
47 → 53 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
216 kW
COP: Pending confirmation
Datasheet V7.0 · 2026-03-05 · EN · p. 2
Electrical input: Not stated (Not stated)
COP scope: Not stated
Test standard: Not stated
EMHP 80F-80F-2-7
R515B
ethanol 26%
1 → -3 °C
water
47 → 53 °C
Heating
Speed: Not stated
Load: Not stated
No subcooler / standard configuration
216 kW
COP: Pending confirmation
Datasheet V7.0 · 2026-03-05 · EN · p. 2
Electrical input: Not stated (Not stated)
COP scope: Not stated
Test standard: Not stated

Related