Engineering guidance
Heat pumps for industrial hot water and process heat
A heat pump can turn a process’s rejected heat into useful hot water when a heat user needs it at the same time, or storage covers the gap. Specify supply temperature, source temperature and operating hours together; the hot-water duties here do not cover steam.
Map the waste-heat stream
Log the waste-heat stream through shifts, shutdowns and cleaning cycles, and set it against the heat demand hour by hour. Where both the cooling and the heating are useful, size on the coincident loads, not on the sum of two nominal ratings.
Check the waste-heat fluid for contamination, corrosion and fouling before choosing the separating heat exchanger. Its approach temperature and pressure drop belong in the cold-side conditions you send for the selection.
Temperatures and production continuity
The EMHP and EMB heating points in the table below are rated at 47 → 53 °C on the hot side, with 26% ethanol at 1 → −3 °C on the cold side. EMHP is the family for higher supply temperatures; confirm any duty above the rated point in a project selection.
Define the process temperature tolerance, the backup capacity and how the process keeps running when the heat pump is out of service.
Reference: Sandvik Coromant, Katowice
At the Sandvik Coromant factory in Katowice, Poland, an EMB-based system with borehole thermal energy storage (BTES) uses waste heat from production. It replaced standalone chillers and gas heating. The factory reports 90% lower gas use and 35% lower electricity use. These are site-level results; they give no machine COP and do not show high-temperature process water.
Models and documented rating conditions
Rating points as printed in each datasheet. Each row describes one operating point, not the full operating envelope. Missing electrical boundaries, loads or speeds are marked in the table.
| Model / refrigerant | Source inlet → outlet | Heated water inlet → outlet | Declared operating point | Thermal capacity / COP | Document / boundary |
|---|---|---|---|---|---|
| EMB 2295-1-4 R1234ze | ethanol 26% 1 → -3 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 114 kW COP: Pending confirmation | Datasheet V3.1 · 2026-06-04 · EN · p. 2 Electrical input: 41.5 kW (compressors only) COP scope: compressors only Test standard: Not stated |
| EMB 2295-1-7 R515B | ethanol 26% 1 → -3 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 114 kW COP: Pending confirmation | Datasheet V3.1 · 2026-06-04 · EN · p. 2 Electrical input: 41.5 kW (compressors only) COP scope: compressors only Test standard: Not stated |
| EMB 2387-1-4 R1234ze | ethanol 26% 1 → -3 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 145 kW COP: 2.84 | Datasheet V3.1 · 2026-06-04 · EN · p. 2 Electrical input: 51.3 kW (compressors only) COP scope: compressors only Test standard: Not stated |
| EMB 2387-1-7 R515B | ethanol 26% 1 → -3 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 145 kW COP: 2.84 | Datasheet V3.1 · 2026-06-04 · EN · p. 2 Electrical input: 51.3 kW (compressors only) COP scope: compressors only Test standard: Not stated |
| EMB 2480-1-4 R1234ze | ethanol 26% 1 → -3 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 175 kW COP: 2.87 | Datasheet V3.1 · 2026-06-04 · EN · p. 2 Electrical input: 61 kW (compressors only) COP scope: compressors only Test standard: Not stated |
| EMB 2480-1-7 R515B | ethanol 26% 1 → -3 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 175 kW COP: 2.87 | Datasheet V3.1 · 2026-06-04 · EN · p. 2 Electrical input: 61 kW (compressors only) COP scope: compressors only Test standard: Not stated |
| EMB 4295-2-4 R1234ze | ethanol 26% 1 → -3 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 229 kW COP: Pending confirmation | Datasheet V3.1 · 2026-06-04 · EN · p. 2 Electrical input: 83 kW (compressors only) COP scope: compressors only Test standard: Not stated |
| EMB 4295-2-7 R515B | ethanol 26% 1 → -3 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 229 kW COP: Pending confirmation | Datasheet V3.1 · 2026-06-04 · EN · p. 2 Electrical input: 83 kW (compressors only) COP scope: compressors only Test standard: Not stated |
| EMB 4387-2-4 R1234ze | ethanol 26% 1 → -3 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 289 kW COP: Pending confirmation | Datasheet V3.1 · 2026-06-04 · EN · p. 2 Electrical input: 102.5 kW (compressors only) COP scope: compressors only Test standard: Not stated |
| EMB 4387-2-7 R515B | ethanol 26% 1 → -3 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 289 kW COP: Pending confirmation | Datasheet V3.1 · 2026-06-04 · EN · p. 2 Electrical input: 102.5 kW (compressors only) COP scope: compressors only Test standard: Not stated |
| EMB 4480-2-4 R1234ze | ethanol 26% 1 → -3 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 350 kW COP: 2.87 | Datasheet V3.1 · 2026-06-04 · EN · p. 2 Electrical input: 122.1 kW (compressors only) COP scope: compressors only Test standard: Not stated |
| EMB 4480-2-7 R515B | ethanol 26% 1 → -3 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 350 kW COP: 2.87 | Datasheet V3.1 · 2026-06-04 · EN · p. 2 Electrical input: 122.1 kW (compressors only) COP scope: compressors only Test standard: Not stated |
| EMHP 36-36-2-4 R1234ze | ethanol 26% 1 → -3 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 85 kW COP: Pending confirmation | Datasheet V7.0 · 2026-03-05 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMHP 36-36-2-7 R515B | ethanol 26% 1 → -3 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 85 kW COP: Pending confirmation | Datasheet V7.0 · 2026-03-05 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMHP 36F-36F-2-4 R1234ze | ethanol 26% 1 → -3 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 100 kW COP: Pending confirmation | Datasheet V7.0 · 2026-03-05 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMHP 36F-36F-2-7 R515B | ethanol 26% 1 → -3 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 100 kW COP: Pending confirmation | Datasheet V7.0 · 2026-03-05 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMHP 44-44-2-4 R1234ze | ethanol 26% 1 → -3 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 98 kW COP: Pending confirmation | Datasheet V7.0 · 2026-03-05 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMHP 44-44-2-7 R515B | ethanol 26% 1 → -3 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 98 kW COP: Pending confirmation | Datasheet V7.0 · 2026-03-05 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMHP 44F-44F-2-4 R1234ze | ethanol 26% 1 → -3 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 116 kW COP: Pending confirmation | Datasheet V7.0 · 2026-03-05 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMHP 44F-44F-2-7 R515B | ethanol 26% 1 → -3 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 116 kW COP: Pending confirmation | Datasheet V7.0 · 2026-03-05 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMHP 60-60-2-4 R1234ze | ethanol 26% 1 → -3 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 135 kW COP: Pending confirmation | Datasheet V7.0 · 2026-03-05 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMHP 60-60-2-7 R515B | ethanol 26% 1 → -3 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 135 kW COP: Pending confirmation | Datasheet V7.0 · 2026-03-05 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMHP 60F-60F-2-4 R1234ze | ethanol 26% 1 → -3 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 161 kW COP: Pending confirmation | Datasheet V7.0 · 2026-03-05 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMHP 60F-60F-2-7 R515B | ethanol 26% 1 → -3 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 161 kW COP: Pending confirmation | Datasheet V7.0 · 2026-03-05 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMHP 80-80-2-4 R1234ze | ethanol 26% 1 → -3 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 181 kW COP: Pending confirmation | Datasheet V7.0 · 2026-03-05 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMHP 80-80-2-7 R515B | ethanol 26% 1 → -3 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 181 kW COP: Pending confirmation | Datasheet V7.0 · 2026-03-05 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMHP 80F-80F-2-4 R1234ze | ethanol 26% 1 → -3 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 216 kW COP: Pending confirmation | Datasheet V7.0 · 2026-03-05 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |
| EMHP 80F-80F-2-7 R515B | ethanol 26% 1 → -3 °C | water 47 → 53 °C | Heating Speed: Not stated Load: Not stated No subcooler / standard configuration | 216 kW COP: Pending confirmation | Datasheet V7.0 · 2026-03-05 · EN · p. 2 Electrical input: Not stated (Not stated) COP scope: Not stated Test standard: Not stated |